4
iLINQ System Configuration
The iLINQ system must be configured to use the room terminal as its source of space temperature and humidity. The
configuration change can be made via the room terminal, iLINQ web interface, or the iLINQ controller onboard LCD. The
iLINQ controller's service password is required for this configuration change.
4.1
Space Temperature and Space Humidity Source - Room Terminal
This method assumes that the room terminal power and pLAN serial communication is connected. Press and hold the
Daikin logo for 3 seconds. Tap the password field, use the keyboard to enter the Service Password (default Service
Password = 1954), and tap the enter icon. Tap the controller display icon and follow the instructions in section 4.2.
1. Press and hold
4.2
Space Temperature and Space Humidity Source - Onboard LCD
If needed, review the iLINQ DDC User Manual for basic operation of the onboard LCD. Login using the iLINQ service
password, scroll to "Unit Config" and press enter. Press the up key and change "Space Temp Src" and "Space Hum Src" to
"Trminal".
1. Enter Service Password
Factory Default = 1954
4.3
Space Temperature and Space Humidity Source - Web Interface
If needed, review the iLINQ DDC User Manual for basic operation of the web interface. Login using the iLINQ service
password(default Service Password = 1954), open the configuration page, and change the space temperature and space
humidity sensor source to terminal.
2. Press and enter Service Password
Factory Default = 1954
3. Press enter icon
Figure 9 - Room Terminal Configuration
2. Select "Unit Config"
Figure 10 - iLINQ Controller Onboard LCD Configuration
4. Press Controller Display
3. Set "Space Temp Src" and "Space Hum Src" to Trminal
12