Installation and Maintenance Manual
Single Duct VAV Terminals
IM 1093-1
Group: Controls
Part Number: IM 1093
Date: February 2015

Advertisement

Table of Contents
loading

Summary of Contents for Daikin IM 1093-1

  • Page 1 Installation and Maintenance Manual IM 1093-1 Group: Controls Part Number: IM 1093 Date: February 2015 Single Duct VAV Terminals...
  • Page 2: Table Of Contents

    Labeling ........6 MQTHI5 Flow Sensor ..... . . 6 IM 1093-1 • SINGLE DUCT VAV TERMINALS www.DaikinApplied.com...
  • Page 3: Introduction

    Never unplug cables, circuit board terminal blocks, or power plugs while power is applied to the panel. Consult your local Daikin representative for warranty details. To find your local Daikin representative, go to NOTICE www.DaikinApplied.com. This equipment generates, uses and can radiate radio...
  • Page 4: Installation

    Store units in a most analog and digital controls may be installed in any clean, dry location prior to installation. Units with controls are orientation. Check with the local Daikin representative for not recommended for use in ambient temperatures greater verification.
  • Page 5: Minimum Clearance For Access

    (flanged outlets optional). A rectangular duct the contractor. size of the terminal outlet should be attached. www.DaikinApplied.com IM 1093-1 • SINGLE DUCT VAV TERMINALS...
  • Page 6: Mqthi5 Single Duct Terminal Units With Electric Heat

    Shows tagging information, customer order number, ETL Logo, etc. • All electric heaters if provided by Daikin are balanced by kW per stage. The installing electrician should rotate 4. AHRI Certification Label on Single Duct Terminal Unit –...
  • Page 7: Troubleshooting

    Never unplug cables, circuit board terminal blocks, or power plugs while power is applied to the panel. Contact your Daikin representative for information concerning controls provided by Daikin. For controls provided by others, contact the local control representative for assistance. www.DaikinApplied.com...
  • Page 8: Specific Electric Heat Troubleshooting Procedures

    This will cause nuisance tripping of the reset switches. Reset the minimum air flow across the coils to the minimum listed value. If further assistance is needed, contact the factory IM 1093-1 • SINGLE DUCT VAV TERMINALS www.DaikinApplied.com...
  • Page 9 Figure 3: MI Flow Sensor Calibration Chart www.DaikinApplied.com IM 1093-1 • SINGLE DUCT VAV TERMINALS...
  • Page 10 Daikin Applied Training and Development Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.