Mitsubishi MELFA RH-6SH Series Standard Specifications Manual page 181

Table of Contents

Advertisement

[Caution] The emergency stop input(terminal block) on the user wiring in the controller can be used for safety
measures as shown in
cable length, so refer to the following and install.
・ Switch contact .......................................... In the case of CR2B-574/CR3-535M controller, prepare a 2-
・ Switch contact capacity........................ Use a contact that operates with a switch contact capacity of
・ Cable length................................................ The length of the wire between the switch and terminal block
・ Emergency stop output capacity....... Set it within 300 mA/24 VDC.
[Reference] The specifications of the RA1 and RA2 coil shown in
・ Rated voltage ............................ DC24V   ± 10%
・ Rated excitation current ...... 12.5mA   ± 10% (at25 deg.)
* Note that these specifications are subject to change without prior notice for modification purposes.
The emergency stop circuit in the robot is a duplex type to ensure safety(CR2B-574 controller only).
Thus, if a 1b contact type is used, faults such as fusing in the emergency stop circuit will not be detected, and
could lead to fires.
If a 1b contact type is used and the emergency stop is input with only one side (across No. 1-2 or No. 5-6), the
contact fusing alarm will occur, and resetting of the alarm will not be possible.
Fig.
6-1. Note that there are limits to the No. of switch contacts, capacity and
contact type.
approx. 1mA to 100mA/24V.
must be max. 15m or less.
Connecting an external device outside of the above range will
cause a controller failure.
Fig. 6-1
are as follow.
6Safety
Safety 5-169