Category 3 Cabling Guidelines (Cxi Ii) - Mitel 3300 ICP Hardware Technical Reference Manual

For mivoice business
Hide thumbs Also See for 3300 ICP:
Table of Contents

Advertisement

C
6
HAPTER
Equipment Room Cabling Guidelines (Continued) (Sheet 5 of 5)
Table 6.3:
Connection
M
N
O
P
Q

Category 3 Cabling Guidelines (CXi II)

Category 5 cable is recommended for all network connections, but the CXi II controller can support Cate-
gory 3 cable subject to the following general guidelines:
Equipment grounds
Patch cable
Metal rack interconnect
Cable tray ground
Cable tray
C
3 C
G
ATEGORY
ABLING
A
B : E
C
PPENDIX
THERNET
ABLING
Guidelines
• Use separate wires to ground
each piece of equipment to the
ground bus bar. If a ground stud
is provided on the back of the
unit, connect it to the ground
bus bar with a dedicated ground
wire (use the gauge specified
by the manufacturer).
• Interconnect Ethernet
equipment supporting 100 Mbps
transmission with CAT 5 UTP
patch cable. Label the cables
and route them neatly through
the channels provided in the
metal rack.
CAUTION: Do not use voice
grade twisted pair interconnect
patch cable wired to standard
voice grade punch-down blocks
on an IDE.
• The metal brackets used to
connect the racks provide
mechanical connection only.
Use a dedicated ground wire to
ground each rack separately to
the ground bus bar.
• Connect the metal racks that
house the Ethernet cable to the
ground bus bar to provide an
effective shield against potential
noise sources such as power
lines and florescent lights.
• The tray should contain
Ethernet cables only. Do not mix
power cables with Ethernet
cables
(CX
II)
UIDELINES
I
G
UIDELINES
132