SuperStorage Server SSG-6049P-E1CR60H/L/L+ User's Manual

System Fans

Five heavy-duty, hot-swappable fans provide cooling for the system. The SC946 features
three fans that can be removed individually and two that are paired in a dual fan module.
The fans an be removed without powering down the system.
Replacing a System Fan
1. With the system on, examine the fans to determine which fan has failed.
2. Simultaneously press down on the upper release tab and push up the lower release tab
of the failed fan.
3. Pull the fan out of the rear of the storage chassis using the handle provided.
4. CAUTION: Fans will continue to rotate for a brief time after removing them from the
storage chassis. To avoid injury, keep fingers clear of the rotating fan blades.
5. Place the new fan into the vacant fan bay.
6. Confirm that the fan is fully seated in the fan bay and functioning properly.
7. The fan will automatically begin running at the correct speed.
3
Figure 3-13. Removing a System Fan
50