Final checks (with burner operating)

 Open the thermostat/pressure switch TL
 Open the thermostat/pressure switch TS
 Turn the gas maximum pressure switch knob to the start
of scale position
 Turn the air pressure switch to the maximum end of
scale position
 Turn the oil maximum pressure switch knob to the start
of scale position
 Turn off the burner and cut off the power
 Disconnect the minimum gas pressure switch connector
 Obscure the flame sensor
Make sure that the mechanical locking systems
on the various adjustment devices are fully tight-
ened.
WARNING
20169116
Start-up, calibration and operation of the burner
The burner must stop
The burner must stop in lockout
The burner must not start
The burner must stop in lockout due to ignition failure