Final Checks (With Burner Operating) - Riello DB 12 SM C03 TC FS1 FB A0 Installation, Use And Maintenance Instructions

Industrial gas burner
Table of Contents

Advertisement

Available languages

Available languages

6.10

Final checks (with burner operating)

➤ Open the thermostat/pressure switch TL
➤ Open the thermostat/pressure switch TS
➤ Turn the gas maximum pressure switch knob to the mini-
mum end of scale position
➤ Turn the air pressure switch to the maximum end of scale
position
➤ Turn off the burner and cut off the power
➤ Disconnect the minimum gas pressure switch connector
➤ Disconnect the wire of the photocell
Make sure that the mechanical locking systems
on the various adjustment devices are fully tight-
ened.
WARNING
20119882
Start-up, calibration and operation of the burner
The burner must stop
The burner must stop in lockout
The burner must not start
The burner must stop in lockout due to ignition failure
28
GB
Tab. K