4.2.4. Valve configuration

Knowing the volume of resin, tank size and specifications of the resin, it is possible to determine the
required valve configuration. The resin specification will give the backwash velocity, as well as the
brine draw and slow rinse velocity that must be respected in order to ensure a proper regeneration of
the unit. From this data, determine the required backwash flow rate as well as the brine draw and
slow rinse flow rate. In most cases, the fast rinse flow rate will be the same as the backwash flow rate,
however for certain valve types the fast rinse flow rate will be the same as the service flow rate.
To determine the backwash flow rate:
Q
= Fs
backwash
backwash
The DLFC installed on the valve has to limit the backwash flow rate to the above calculated flow rate.
To determine the injector size:
The velocities to be respected for brine draw and slow rinse are given on the resin manufacturer
specifications. Generally speaking, the injector has to allow a flow rate of about 4 BV / h
(corresponding to the flow rate of brine being drawn added to the flow rate of raw water passing
through the injector nozzle to create the suction effect).
Q
= 4 x BV / h
Inj
Note
This value does not correspond to the brine draw flow rate but to the total flow rate passing
through the injector. Then refer to the injector diagrams at the inlet pressure in order to
check if the injector will give a correct flow rate. See chapters 4.4.1. 1600 Injectors, page 33
and 4.4.2. 1650 Injectors, page 34.
Ref. MKT-IM-020 / B - 08.06.2018
x S
Installer Manual Fleck 9000 - SXT - System sizing
with:
Q
: backwash flow rate [m
backwash
Fs
: backwash velocity [m/h]
backwash
S: Tank
[m
cross section area
with:
Q
: total flow rate passing through the injector [L/h]
inj
BV: bed volume of resin [L]