• In Bypass mode, output voltage of the UPS is still present. In order to cut
off the output, switch off the line input breaker. The LCD display will turn
off and UPS is now completely off.
8. Turn off the UPS without utility power supply in Battery mode
• Touch "CONTROL" and select "Off UPS" icon to turn off the UPS. Refer
to "On/Off UPS" screen.
• Then UPS will cut off power to output terminals.
9. Mute the buzzer
• Touch "SETTING" and select "GENERAL" item. There are two events
available to mute. Refer to "SETTING" screen.
• Some warning alarms can't be muted unless the error is fixed. Please
refer to section 3-3 for details.
10. Operation in warning status
• When LCD screen shows "Fault Mode" and the buzzer beeps once every
second, it indicates that there are problems for UPS operation. Users can
read the warning message(s) from "DATA LOG" menu. Please refer to the
Chapter 4 for details.
• Some warning alarms can't be muted unless the error is fixed. Please
refer to section 3-3 for details.
11. Operation in Fault mode
• When the buzzer beeps continuously, it means that there is a fatal
error with the UPS. Users can get the fault code from "DATA LOG" menu.
Please refer to the Chapter 4 for details.
• Please check the loads, wiring, ventilation, mains, battery and so on after
the fault occurs. Don't try to turn on the UPS again before solving the
issues. If the problems persist, contact the distributor or service personnel
immediately.
• In case of an emergency, shut off connections from mains, external
battery, and output immediately to avoid possible damage to the UPS or
equipment.