This parameter setting is related to "Shutdown Voltage" setting. The
setting value should be higher than "Shutdown Voltage" setting.
Shutdown Voltage: If battery voltage is lower than this point in
battery mode, UPS will automatically shut down. The setting range is
10.5V ~ 12.0V. 10.7V is default setting (This setting is only available for
long-run model).
Battery age: if battery age is beyond the setting month, then the UPS
will alarm for reminding. The factory default setting is 24 months.
Battery AH: setting battery capacity.
Battery Groups: setting battery groups.
Battery Study:
Enable: The backup time prediction has a self-learning function to
calibrate the battery virtual capacity according to a complete charging and
discharging process.
Disable: The battery capacity will not be updated during the charging
and discharging process.
Battery Initial: The battery virtual capacity is initialized to 100%.
Because the backup time has self-learning function, after the battery
is used for along time, after each full charge is completed, the virtual
capacity of the battery will be continuously updated. After replacing the
new battery, the virtual of the battery needs to be initialized at this time.
Battery Cali: Calibration backup time.
Battery TEMPCMPN(Compensation): It will compensate charging
voltage based on temperature.