BATT Number: The total number of installed battery. (It's required to
restart the UPS after setting.) The setting range is 16 ~ 20 pcs. 16 pcs is
default setting.
Charger VOLT: The setting point of battery float voltage. 13.6V is
default setting.
UPS Type: There are two options, HV and LV. This change is only
allowed for qualified technician.
NOTE: It's required torestart the UPS after setting.
Power Set: Set the UPS power.
Output Set: There are two options, 3-3 and 3-1. This change is only
allowed for qualified technician.
INSTALL
NOTE: It's required torestart the UPS after setting.
D Password: Enable or disabledynamic password.
CustomerID: Used to produce dynamic password.
INSTALL
System Install Date: Set the date of UPS installation.
Battery Install Date: Set the date of Battery installation.
Date/Time: Set the date and time. The format is YYYY-MM-DD
HH:MM:SS. The calendar day will be automatically changed when the
year, month and date are set.
34
INSTALL Page
INSTALL Page