WARNING
● Make sure a DC breaker or other protective device between
UPS and the external battery pack is installed for added safety. If
not, please install it carefully. Switch off the battery breaker before
installation.
NOTE: Set the battery pack breaker in "OFF" position and then
install the battery pack.
● Pay special attention to the rated battery voltage marked on
the rear panel. If you want to change the numbers of the battery
in a chain, make sure you modify the UPS setting accordingly.
Connection with wrong battery voltage may cause irreversible
damage of the UPS.
● Pay special attention to the polarity marking on external battery
terminal block. Connection with wrong battery voltage may cause
irreversible damage of the UPS.
● Make sure the protective grounding/earthing wiring is adequate.
The current spec, color, position, connection and conductance
reliability of the wire should be verified.
● Make sure the utility input & output wiring is rated correctly.
The current spec, color, position, connection 8 and conductance
reliability of the wire should be verified. Make sure the L/N side is
correct, not reverse or short-circuited.
2.4 UPS Installation for Parallel System
If the UPS is only for single operation, you may skip this section.
1) Install and wired the UPS according to the section 2-3.
2) Connect the output wires of each UPS to an output breaker.
3) Connect all output breakers to a major breaker. This major output
breaker will then connect directly to the loads.
4) Either common battery packs or independent battery packs for each
UPS are allowed.