Pier Or Beam Mount - Carrier Aero 39MN MW03-110 Series Installation, Start-Up And Service Instructions Manual

Indoor and weathertight outdoor air handlers
Table of Contents

Advertisement

The 14 in. tall curbs weigh 6 lb per linear foot; 24 in. curbs weigh
9 lb per linear foot.
IMPORTANT: Verify installed curb dimensions before
attempting to rig the unit and install it on the curb.
Due to the pressure capabilities of the 39 Series air handlers, duct
connections must be gasketed and screwed to the unit to prevent
leakage. Refer to Duct Connections section on page 95. No provi-
sions have been made to attach the ductwork to the curb. Dimen-
sions for inlet and discharge locations are shown in drawings pro-
duced in AHUBuilder
program.
®
UNIT CURB
CURB GASKET
(OPTIONAL)
Fig. 20 — Splice Plate Usage
HEX HEAD
BOLT
END
UNIT CURB
Fig. 21 — Corner Bracket
Fig. 22 — Fasten Cross Supports
CURB SPLICE
PLATE
FLAT WASHER
SEAL STRIP
HEX NUT
LOCK
WASHER
SIDE
CORNER BRACKET
UNIT CURB
CURB
CHANNEL
The return and supply ducts must be supported independently
from the unit. Do not exert weight or downward force on the unit
other than minimal force required to attach ductwork.
Before the unit is installed, gasketing must be installed between
the curb and unit as shown in Fig. 23. This gasket material is sup-
plied by the curb manufacturer. If gasket is not supplied with the
curb, recommended field-supplied gasket material is 1/2-in. thick
by 2-in. wide closed cell neoprene.
When curb is installed, place gasket on curb without stretching or
overlapping the material, which can cause gaps or leaks. Butt all
joints evenly and avoid creating gaps where water can leak into
the curb. Make sure seams in gasket material overlap seams in the
curb rail. See Fig. 23 for installation details.
After gasket is in place, rig unit into position as described in Rig-
ging and Handling section. Locate unit on curb so it is correctly
oriented with respect to the curb inlet and discharge locations.
On curb installations, lower the unit directly into place, ensuring
that the roof curb gasket does not shift or curl.
RAIL SEAM
RAIL SEAM
Fig. 23 — Install Gasketing

Pier or Beam Mount

As an alternative to curb mounting, units can also be mounted on
I-beams or piers. For units mounted on I-beams, the beams must
run the continuous length of the unit. If seismic criteria apply,
crosspieces must be added between the beams, according to seis-
mic calculations. For pier-mounted units, one pier must be in-
stalled in each corner of the unit, at the junction of the base rail
corners.
For each additional 8 ft of length, for size 03-110 units, install one
additional pier on each size of the unit at the junction of each
section split underneath the base rails. See Fig. 24 for a typical
installation.
91
BUTT JOINTS, DO
NOT OVERLAP
GASKET SEAM
WRONG METHOD
GASKET SEAM
RIGHT METHOD

Advertisement

Table of Contents
loading

Table of Contents