Belt Drive Plenum Fans; Direct Drive Plenum Fans With Nema - Carrier Aero 39MN MW03-110 Series Installation, Start-Up And Service Instructions Manual

Indoor and weathertight outdoor air handlers
Table of Contents

Advertisement

DRIVE PULLEY
NOMINAL
TORQUE
SCREW SIZE
(in.-lb)
9
NO. 6
NO. 8
16
30
NO. 10
70
1/4
140
5/16
3/8
216
Fig. 176 — Fan, Shaft and Bearing Details —
Roller — Extended Race, One or Both Sides
TORQUE TABLE
CAPSCREW AND
HEX HEAD
SETSCREW
ACROSS
SIZE (NO./in.)
FLATS (in.)
10
/
3
32
1
/
/
1
4
5
/
/
5
16
32
/
3
3
/
8
16
/
7
7
/
16
32
/
1
1
/
2
/
5
5
/
8
16
3
/
3
/
4
BEARING HOLDDOWN BOLT TORQUE
BOLT SIZE (in.)
TORQUE (ft-lb)
3
/
- 16
30
8
/
- 13
63
1
2
/
- 11
5
100
8
/
- 10
3
165
4
Fig. 177 — Fan, Shaft and Bearing Details —
Squeeze-Type Locking Collar
SQUARE HD
ACROSS
TORQUE
FLATS (in.)
25 in.-lb
60 in.-lb
8
10 ft-lb
17 ft-lb
25 ft-lb
1
/
40 ft-lb
4
2
90 ft-lb
125 ft-lb
8

BELT DRIVE PLENUM FANS

Start-up procedures for plenum fans are similar to those for airfoil
or forward-curved fans described in the preceding section. Also
refer to the fan manufacturer's Installation, Operation, and Main-
tenance instructions shipped with the plenum fan section for fur-
ther details.
DIRECT DRIVE PLENUM FANS WITH NEMA MOTORS
Start-up procedures are similar to those for fans described above
with the following additions:
1. Check tightness of bolts securing fan motor to base.
2. Check tightness of fan wheel bushing bolts (see Fig. 178) per
Table 44 below.
Table 44 — Bushing Bolt Torque
BUSHING TYPE
JA
SD
SK
SF
3. Visually verify the radial clearance between the fan wheel
and the inlet cone is equal in all directions.
4. Verify the fan wheel to inlet cone overlap (see Fig. 178) is
within limits per Table 45 below.
5. Turn the fan wheel by hand to ensure no contact with inlet
cone.
6. If provided with piezometer ring, verify all tubing connec-
tions are secure.
Table 45 — Inlet Cone Overlap
WHEEL SIZE
105
122
135
150
165
182
200
222
245
270
300
330
365
402
7. Ensure VFD has been programmed with the correct maxi-
mum fan speed and maximum output frequency to limit mo-
tor speed (rpm) to fan maximum speed (rpm).
a. See label on fan sled for maximum fan speed (rpm).
b. Check VFD for maximum fan speed (parameter 2002) to
ensure that the fan maximum speed is the VFD maxi-
mum speed.
c. Using the Parameters Mode (page 160) on the VFD, ver-
ify that parameter 2002 has been changed to the value
shown on the fan label. If it does not match, DO NOT
start the unit. Press Edit (Soft Key 2) to enter correct
value for parameter 2002. Press Exit (Soft Key 1).
d. See motor nameplate for operating frequency (Hz) and
speed (rpm).
206
TORQUE (in.-lb)
72
108
180
360
WHEEL - CONE OVERLAP (in.)
0.12 - 0.29
0.12 - 0.32
0.12 - 0.34
0.19 - 0.41
0.25 - 0.47
0.31 - 0.50
0.38 - 0.57
0.44 - 0.63
0.50 - 0.69
0.56 - 0.76
0.62 - 0.88
0.75 - 0.96
0.81 - 1.13
0.88 - 1.26

Advertisement