FAULT CODE
FAULT NAME IN PANEL
1
OVERCURRENT
2
DC OVERVOLT
3
DEV OVERTEMP
4
SHORT CIRC
5
OVERLOAD
6
DC UNDERVOLT
7
AI1 LOSS
8
AI2 LOSS
9
MOT OVERTEMP
10
PANEL LOSS
11
ID RUN FAIL
12
MOTOR STALL
13
RESERVED
14
EXT FAULT 1
15
EXT FAULT 2
16
EARTH FAULT
17
UNDERLOAD
18
THERM FAIL
19
OPEX LINK
20
OPEX PWR
21
CURR MEAS
22
SUPPLY PHASE
23
RESERVED
24
OVERSPEED
25
RESERVED
26
DRIVE ID
27
CONFIG FILE
28
SERIAL 1 ERR
29
EFB CON FILE
30
FORCE TRIP
31
EFB1
32
EFB2
33
EFB3
34
MOTOR PHASE
35
OUTP WIRING
101-105
SYSTEM ERROR
201-206
SYSTEM ERROR
1000
PAR HZRPM
1001
PAR PFA REFNG
1002
PAR PFA IOCNF
Table 52 — Fault Codes
DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION
Output current is excessive. Check for excessive motor load, insufficient acceleration time (parameters
2202 ACCELER TIME 1, default 30 seconds), or faulty motor, motor cables or connections.
Intermediate circuit DC voltage is excessive. Check for static or transient over voltages in the input
power supply, insufficient deceleration time (parameters 2203 DECELER TIME 1, default 30 seconds),
or undersized brake chopper (if present).
Drive heat sink is overheated. Temperature is at or above 115°C (239°F). Check for fan failure, obstruc-
tions in the airflow, dirt or dust coating on the heat sink, excessive ambient temperature, or excessive
motor load.
Fault current. Check for short-circuit in the motor cable(s) or motor or supply disturbances.
Inverter overload condition. The drive output current exceeds the ratings.
Intermediate circuit DC voltage is not sufficient. Check for missing phase in the input power supply,
blown fuse, or under voltage on main circuit.
Analog input 1 loss. Analog input value is less than AI1 FLT LIMIT (3021). Check source and connec-
tion for analog input and parameter settings for AI1 FLT LIMIT (3021) and 3001 AI<MIN FUNCTION.
Analog input 2 loss. Analog input value is less than AI2 FLT LIMIT (3022). Check source and connec-
tion for analog input and parameter settings for AI2 FLT LIMIT (3022) and 3001 AI<MIN FUNCTION.
Motor is too hot, as estimated by the drive. Check for overloaded motor. Adjust the parameters used for
the estimate (3005 through 3009). Check the temperature sensors and Group 35 parameters.
Panel communication is lost and either drive is in local control mode (the control panel displays LOC),
or drive is in remote control mode (REM) and is parameterized to accept start/stop, direction or refer-
ence from the control panel. To correct, check the communication lines and connections. Check param-
eter 3002 PANEL COMM ERROR, parameters in Group 10: Command Inputs and Group 11:
Reference Select (if drive operation is REM).
The motor ID run was not completed successfully. Check motor connections.
Motor or process stall. Motor is operating in the stall region. Check for excessive load or insufficient
motor power. Check parameters 3010 through 3012.
Not used.
Digital input defined to report first external fault is active. See parameter 3003 EXTERNAL FAULT 1.
Digital input defined to report second external fault is active. See parameter 3004 EXTERNAL FAULT
1.
The load on the input power system is out of balance. Check for faults in the motor or motor cable. Ver-
ify that motor cable does not exceed maximum specified length.
Motor load is lower than expected. Check for disconnected load. Check parameters 3013 UNDER-
LOAD FUNCTION through 3015 UNDERLOAD CURVE.
Internal fault. The thermistor measuring the internal temperature of the drive is open or shorted. Con-
tact Carrier.
Internal fault. A communication-related problem has been detected between the OMIO and OINT
boards. Contact Carrier.
Internal fault. Low voltage condition detected on the OINT board. Contact Carrier.
Internal fault. Current measurement is out of range. Contact Carrier.
Ripple voltage in the DC link is too high. Check for missing main phase or blown fuse.
Not used.
Motor speed is greater than 120% of the larger (in magnitude) of 2001 MINIMUM SPEED or 2002
MAXIMUM SPEED parameters. Check parameter settings for 2001 and 2002. Check adequacy of
motor braking torque. Check applicability of torque control. Check brake chopper and resistor.
Not used.
Internal fault. Configuration block drive ID is not valid.
Internal configuration file has an error. Contact Carrier.
Field bus communication has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019
COMM FAULT TIME). Check communication settings (Group 51 or 53 as appropriate). Check for poor
connections and/or noise on line.
Error in reading the configuration file for the field bus adapter.
Fault trip forced by the field bus. See the field bus reference literature.
Fault code reserved for the EFB (Embedded Field Bus) protocol application. The meaning is protocol
dependent.
Fault code reserved for the EFB protocol application. The meaning is protocol dependent.
Fault code reserved for the EFB protocol application. The meaning is protocol dependent.
Fault in the motor circuit. One of the motor phases is lost. Check for motor fault, motor cable fault, ther-
mal relay fault (if used), or internal fault.
Error in power wiring suspected. Check that input power wired to drive output. Check for ground faults.
Error internal to the drive. Contact Carrier and report the error number.
Error internal to the drive. Contact Carrier and report the error number.
Parameter values are inconsistent. Check for any of the following:
2001 MINIMUM SPEED > 2002 MAXIMUM SPEED
2007 MINIMUM FREQ > 2008 MAXIMUM FREQ
2001 MINIMUM SPEED / 9908 MOTOR NOM SPEED is outside of the range: –128 to +128
2002 MAXIMUM SPEED / 9908 MOTOR NOM SPEED is outside of the range: –128 to +128
2007 MINIMUM FREQ / 9907 MOTOR NOM FREQ is outside of the range: –128 to +128
2008 MAXIMUM FREQ / 9907 MOTOR NOM FREQ is outside of the range: –128 to +128
Parameter values are inconsistent. Check that 2007 MINIMUM FREQ is negative, when 8123 PFA
ENABLE is active.
Parameter values are inconsistent. The number of programmed PFA relays does not match with Inter-
lock configuration, when 8123 PFA ENABLE is active. Check consistency of RELAY OUTPUT parame-
ters 1401 through 1403, and 1410 through 1412. Check 8117 NR OF AUX MOTORS, 8118
AUTOCHANGE INTERV, and 8120 INTERLOCKS.
271