Control Dampers; Damper Linkage Adjustment; Linkage Adjustment - Carrier Aero 39MN MW03-110 Series Installation, Start-Up And Service Instructions Manual

Indoor and weathertight outdoor air handlers
Table of Contents

Advertisement

CONTROL DAMPERS

Control dampers may be operated with pneumatic or electric actu-
ators. These items should be set up in accordance with the control
manufacturer's installation instructions.

DAMPER LINKAGE ADJUSTMENT

After the air-handling unit has been powered, the dampers should
be checked to ensure they move freely and close tightly. Adjust-
ment of the linkage may be required.

LINKAGE ADJUSTMENT

1.
With the damper actuator unpowered and the damper linkage
disconnected, rotate the outdoor-air damper so that it is fully
closed. Make sure the spring return actuator has completed its
Fig. 45 — Zone Damper Assembly Details (Horizontal Discharge Shown)
stroke (with power disconnected this will be achieved). The
return-air damper should be fully open at this point.
2.
Tighten the actuator on the damper jackshaft, ensure all link-
age is connected, secure and moves freely.
3.
With power applied to the actuator, check for a complete
stroke and free movement in dampers and damper linkage.
.
Dampers and linkage must be checked prior to applying
power. Make certain that there are no obstructions that could
interfere with the operation of the dampers, or equipment
damage could result.
106
CAUTION
a39-2970