Ariston COMPACT M NET R32 Technical Instructions For Installation page 67

Table of Contents

Advertisement

Menu.
Sub-menu.
Parameter
4
Zone 1 parameters
4.
0
Setpoint
4.
0.
0 T Day
4.
0.
1 T Night
4.
0.
2 T set Z1
4.
0.
3 Zone frost temperature
4.
1
Automatic winter mode
4.
1.
0 Automatic winter mode activation
4.
1.
1 Automatic winter mode threshold
4.
1.
2 Automatic winter mode delay time
4.
2
Settings
4.
2.
0 Zone temperature range
4.
2.
1 Thermoregulation
4.
2.
2 Slope
4.
2.
3 Paral shift
4.
2.
4 Room Influence Proportional
4.
2.
5 Max T
4.
2.
6 Min T
4.
2.
7 Thermoregulation logic
4.
2.
8 Quick night setback
4.
2.
9 Heat request mode
4.
3
Diagnostics
4.
3.
0 Room T
4.
3.
1 Room T setpoint
4.
3.
2 Flow temperature
4.
3.
3 Return temperature
4.
3.
4 Heat Request Z1
4.
3.
5 Pump status
4.
3.
7 Relative humidity
4.
3.
8 Zone flow temperature setpoint
4.
4
Zone module settings
4.
4.
0 Zone pump modulation
4.
4.
1 Target deltaT for pump modulation
Description
Default
19°C Heat - 24°C
10-30°C
Cool
13°C Heat - 30°C
10-30°C
Cool
40 [HT] - 20 [LT]
par 4.2.5 - par 4.2.6
5°C
2-15°C
0 = OFF
0
1 = ON
20°C
10-30°C
300
0-600
0 = Low Temp[LT]
1
1 = High Temp[HT]
0 = Fix Flow T
1 = Basic Thermoreg
1
2 = Room T Only
3 = Outdoor T Only
4 = Room+Outdoor T
0.6 [LT] or 1.5 [HT] 0.2-1 [LT] or 0.4-3.5 [HT]
0
-14 +14 [HT] or -7 +7 [LT]
10 [HT] or 2 [LT]
0-20
60 [HT] or 45 [LT]
20-70 [HT] or 20-45 [LT]
20 [HT] or 20 [LT]
20-70 [HT] or 20-45 [LT]
0 = Classic
0
1 = Smart
0 = OFF
0
1 = ON
0 = Standard
1 = RT Time Programs Exclu-
0
sion
2 = Forcing Heat Demand
0 = OFF
1 = ON
0 = OFF
1 = ON
0 = Fixed
1
1 = Modulating on DeltaT
2 = Modulating on pressure
20 [HT] or 7 [LT]
4-25
Commissioning
Range - Value
Visible only
with Zone
Module
Visible only
with Zone
Module
Visible only
with Zone
Module
Visible only
with Zone
Module
Visible only
with Zone
Module
67 / EN
Notes