1.12.5 Floor drying cycle
Defines the screed drying programme for under-floor systems
using the following values:
0
OFF
1
Functional (screed heating at a fixed temperature of
25°C for 3 days, then at the temperature defined by Par.
1.12.6)
60
50
40
30
20
10
0
0
1
2
3
2
Ready to Use (heating of the screed at a variable tem-
perature from 25°C to the temperature defined by Par.
1.12.6, according to the period indicated as an example
in the graph for an 18-day period)
set point 55°C
60
40
20
0
0
2
4
6
3
Functional + Ready to Use (screed heating at a fixed
temperature of 25°C for 3 days, then for a further 4 days
at the temperature defined by Par. 1.12.6, then at a vari-
able temperature from 25°C to the temperature defined
by Par. 1.12.6, according to the period indicated as an
example in the graph for an 18-day period)
set point 55°C
80
60
40
20
0
0
5
10
4
5
6
7
8
Period (days)
Fig. 97
set point 40°C
8
10 12 14 16 18 20
Period (days)
Fig. 98
set point 60°C
15
20
25
Period (days)
Fig. 99
4
Ready to Use + Functional (heating of the screed at a
variable temperature from 25°C to the temperature de-
fined by Par. 1.12.6, according to the period indicated as
an example in the graph for an 18-day period, then at
a fixed temperature of 25°C for a period of 3 days, then
for a further 4 days at the temperature defined by Par.
1.12.6)
60
50
40
30
20
10
0
9
0
5
Manual (screed heating at the temperature set in Par.
1.12.6)
1.12.6 Floor drying Flow Set Point T
Defines the set-point temperature of the heating delivery dur-
ing the screed drying function (see Par. 12.8.1).
1.12.7 Floor drying total Remaining Days
Defines the days remaining for the screed drying function.
1.12.8 Dhw rating mode
Defines the test operation mode in DHW mode.
1.12.9 Exogel kit activation
Enables integration of the anti-freeze kit.
1.16 EM DIAGNOSTICS - 1 INPUT
Displays the values of the system's board inputs.
1.18 EM DIAGNOSTICS - 1 OUTPUT
Displays the values of the system's board outputs.
1.20 SYSTEM INTEGRATION
1.20.0 PV offset DHW setpoint temperature
Press the selector
value to increase the DHW set-point during integration from
the photovoltaic system.
1.20.2 Tank solar integration
Activates integration of the solar heating system. In this case,
the high sensor of the solar heating calorifier is used as a DHW
calorifier sensor.
1.20.3 OpenTherm gateway activation
Activates the Opentherm gateway.
1.21 ERROR HISTORY
Displays the last 10 errors.
30
1.22 RESET MENU
Restores the default settings.
5
10
15
20
Period (days)
. Rotate the selector
to set the desired
57 / EN
Commissioning
25
30
Fig. 100