Temperature Adjustment - Ariston COMPACT M NET R32 Technical Instructions For Installation

Table of Contents

Advertisement

6.7

Temperature adjustment

Simultaneously press the "Esc" and "Menu" buttons until "Insert
Code" appears on the display.
Turn the selector to enter the technical code (234) then press
the selector
to confirm; the display will show TECHNICAL
AREA.
Turn the selector
to choose the desired item.
– COMPLETE MENU
Press the selector
. Turn the selector
sired item.
4
ZONE 1 PARAMETERS
4.1
AUTOMATIC WINTER MODE
4.1.0 Activation of the auto summer/winter function
[ON, OFF]
4.1.1 Auto summer/winter temperature limit
Turn the selector and set the threshold temperature of the
auto summer/winter function.
4.1.2 Summer/winter switching delay
Turn the selector and set the auto summer/winter switching
delay.
Press the selector
. Turn the selector
sired item.
4.2
ZONE 1 SETTING
4.2.0 Z1 T range
Turn the selector and select the temperature range:
0 - low temperature
1 - high temperature
4.2.1 Temperature adjustment
Press the selector
. Turn the selector
temperature control installed:
0 - Fix Flow T
1 - Basic Thermoreg
2 - Room T Only
3 - Outdoor T Only
4 - Room+Outdoor T
58 / EN
4.2.2 Slope
Press the selector
accordance with the type of heating system.
Press the selector
Low-temperature system (under-floor panels) curve between
0.2 and 0.8
High-temperature system (radiators) curve between 1.0 and
3.5
The checking process for the suitability of the curve requires a
long period of time during which several adjustments may be
to choose the de-
necessary. When the outdoor temperature falls (winter) three
conditions may arise:
– The temperature of the room may fall, indicating that a
– The temperature of the room may rise, indicating that a
– The temperature of the room remains constant, indicat-
Once you have found the curve which maintains the room
temperature at a constant level, check the actual temperature
value.
to choose the de-
and set the type of
1
Delivery temperature to the system
2
Delivery value room temperature
3
Outside air temperature
4
Low temperature
5
High temperature
. Turn the selector and set the curve in
to confirm.
steeper curve should be set.
gentler curve should be set.
ing that the set curve is exactly right.
3.5
3.0
°C
100
90
80
70
1
60
50
40
30
10
5
0
2
Commissioning
2.5
2.0
1.5
5
1.2
1.0
0.8
0.6
4
0.4
0.2
-5 -10 -15 -20 °C
3
Fig. 101