Ariston COMPACT M NET R32 Technical Instructions For Installation page 53

Table of Contents

Advertisement

1.1.3 AUX input 1
Press the selector
. Turn the selector
sired item.
0
None.
1
Humidity sensor: when the contact is closed, the heat
pump is turned off during the cooling cycle. Use Par.
1.1.9 to set which zone pumps will stop as a result.
2
Heating/Cooling from External Request mode: when
the contact is closed, the operating mode is set to cool-
ing; when the contact is opened, the operating mode is
set to heating.
3
Thermostat TA3: the signal is interpreted as a contact for
a thermostat in zone 3. When the contact is closed, it is
sent as a heat request for zone 3.
4
Safety Thermostat: connect an under-floor safety ther-
mostat to the contact. When the contact is closed, wa-
ter circulation is interrupted.
5
Photovoltaic input active: input not active (0V), no inte-
gration.
Input active (230 V), the energy surplus is used to in-
crease the DHW set-point by the quantity defined
through parameter 1.20.0 - Delta T Setpoint DHW pho-
tovoltaic. If the DHW calorifier has reached the new set-
point, it is possible to use this energy to increase the
set-point of the inertial storage tank (if present) through
parameter 20.4.4 or of the heating / cooling function to
the comfort set-point.
1.1.4 AUX input 2
Press the selector
. Turn the selector
sired item.
0
None.
1
Humidity sensor: when the contact is closed, the heat
pump is turned off during the cooling cycle. Use Par.
1.1.9 to set which zone pumps will stop as a result.
2
Heating/Cooling from External Request mode: when
the contact is closed, the operating mode is set to cool-
ing; when the contact is opened, the operating mode is
set to heating.
3
Thermostat TA3: the signal is interpreted as a contact for
a thermostat in zone 3. When the contact is closed, it is
sent as a heat request for zone 3.
4
Safety Thermostat: connect an under-floor safety ther-
mostat to the contact. When the contact is closed, wa-
ter circulation is interrupted.
5
Photovoltaic input active: input not active (0V), no inte-
gration.
Input active (230 V), the energy surplus is used to in-
crease the DHW set-point by the quantity defined
through parameter 1.20.0 - Delta T Setpoint DHW pho-
tovoltaic. If the DHW calorifier has reached the new set-
point, it is possible to use this energy to increase the
set-point of the inertial storage tank (if present) through
parameter 20.4.4 or of the heating / cooling function to
the comfort set-point.
1.1.5 Electric heat sources blocking type
to choose the de-
Press the selector
sired item.
0
1
2
3
1.2
1.2.0 AUX output 1
0
1
2
3
4
5
6
7
to choose the de-
1.2.1 AUX output 2
0
1
2
3
4
5
6
7
. Turn the selector
None. The company block function is not specified.
Soft lockout. The energy provider can send a signal.
Hard lockout.
Hybrid lockout.
OUTPUT CONFIGURATION
None.
Error alarm: the contact is closed in case of a system er-
ror.
Humidistat alarm: the contact is closed when the AUX1
input is set as a humidistat and the contact is closed.
Heating and DHW external request: the contact is
closed to generate a heat request towards an external
source for space heating and DHW.
Cooling request: the contact is closed to generate a
cooling request towards an external source.
External DHW request: the contact is closed to generate
a heating request towards an external source for DHW.
Heating / Cooling mode: the contact is closed when
the cooling operating mode is active. The contact is
opened when the operating mode is heating or stand-
by.
External heating request: the contact is closed to gen-
erate a heating request towards an external source for
space heating.
None.
Error alarm: the contact is closed in case of a system er-
ror.
Humidistat alarm: the contact is closed when the AUX1
input is set as a humidistat and the contact is closed.
Heating and DHW external request: the contact is
closed to generate a heat request towards an external
source for space heating and DHW.
Cooling request: the contact is closed to generate a
cooling request towards an external source.
External DHW request: the contact is closed to generate
a heating request towards an external source for DHW.
Heating / Cooling mode: the contact is closed when
the cooling operating mode is active. The contact is
opened when the operating mode is heating or stand-
by.
External heating request: the contact is closed to gen-
erate a heating request towards an external source for
space heating.
Commissioning
to choose the de-
53 / EN