Appendix C: Electronics verification
January 2013
C.2

Electronics verification

Electronics functionality can be verified via two different verification methods:
Both methods require the use of a Field Communicator or AMS. It is not required to disconnect
the sensor to perform the electronics verification since the transmitter is capable of
disconnecting the sensor signal at the input to the electronics. Should the user choose to
physically disconnect the sensor from the electronics, refer to
on page
C.2.1

Electronics verification using flow simulation mode

Field Comm.
Electronics verification can be done by utilizing the internal flow simulation functionality. This
functionality is available as model option code DS1 at the time of order. The Rosemount 8600D
is capable of simulating either a fixed flow rate or a varying flow rate. The amplitude of the
simulated flow signal is based on the minimum required process density for the given line size
and service type. Either type of simulation (fixed or varying) will effectively disconnect the
Rosemount 8600D sensor from the electronics charge amplifier input (see
72) and replace it with the simulated flow signal.
C.2.2

Fixed flow rate simulation

Field Comm.
The fixed flow simulation signal can be entered in either percent of range or flow rate in the
current engineering units. The resulting flow rate and/or shedding frequency can be
continuously monitored via a Field Communicator or AMS.
C.2.3

Varying flow rate simulation

Field Comm.
The profile of the varying flow simulation signal is a repetitive triangular waveform as illustrated
in
Figure
entered as a flow rate in the current engineering units. The ramp time can be entered in seconds
from a minimum of 0.6 seconds to a maximum of 34951 seconds. The resulting flow rate and/or
shedding frequency can be continuously monitored via a Field Communicator or AMS.
Note
To manually disconnect the sensor for precautionary measures, see
housing on page 79
120
Flow Simulation Mode
Using an External Frequency Generator
79.
1, 2, 4, 3, 1
1, 2, 4, 3, 1, 1
1, 2, 4, 3, 1, 2
C-1. The minimum and maximum flowrate can be entered in either percent of range or
for details.
Get other manuals https://www.bkmanuals.com
Reference Manual
00809-0100-4860, Rev BC
Replacing the electronics housing
Figure 5-2 on page
Replacing the electronics
Electronics verification