Coaxial Cable At The Electronics Housing - Emerson Rosemount 8600D Series Reference Manual

Vortex flowmeter
Hide thumbs Also See for Rosemount 8600D Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4860, Rev BC
Attach the meter adapter
1.
2.
3.
4.
Connect the coaxial cable at the meter body
1.
Note
Do not stretch the sensor cable over 1.5-in. (40 mm) beyond the top of the bracket. Damage to
the sensor may occur if the sensor cable is stressed.
2.
3.
4.
5.6.6

Coaxial cable at the electronics housing

Remove the coaxial cable from the electronics housing
1.
2.
3.
4.
Troubleshooting
If you are using a conduit adapter or cable gland, slide it over the plain end of the coaxial
cable (the end without a ground wire).
Slide the meter adapter over the coaxial cable end.
Use a
5
/
-in. (8 mm) open end wrench to securely tighten the sensor cable nut onto one
16
end of the union.
Place the union onto the two screws extending out of the meter adapter and tighten
the two screws.
Pull the sensor cable out of the bracket slightly and securely tighten the sensor cable
nut onto the union.
Place the meter adapter into the top of the bracket and line up the screw holes.
Use a hex wrench to turn the three adapter screws counterclockwise (outward) to
engage the bracket.
Tighten the conduit adapter or cable gland into the
meter adapter.
Loosen the two housing screws from the housing adapter.
Remove the housing adapter from the housing.
Loosen and remove the coaxial cable nut from the base of the electronics housing.
Remove the coaxial cable ground connection from the housing base by loosening the
housing base screw that is connecting it to the housing base.
Get other manuals https://www.bkmanuals.com
Section 5: Troubleshooting
January 2013
85