Download Print this page

Sinclair SDV 6 SWC-61 User & Installation Manual page 45

Advertisement

Parameter
Parameter Name
Code
Fan speed setting in
N20
heating standby
mode
Time to stop the fan
N21
of IDU (Termal)
EXV opening
N22
selection during
heating standby
Cooling return
N23
difference
temperature
Heating return
N24
difference
temperature
IDU heating
N25
temperature
compensation
Default
Parameter Range
Value
0/1/14
0
01/02/03/04
01
00/01/02/14
14
00/01/02/03/04
00
00/01/02/03/04
00
00/01/02/03/04
00
42
Remarks
0: Termal
1: Speed 1
14: Speed 1,The fan speed display by controller is
based on before going to standby mode.
01: 4min
02: 8min
03: 12min
04: 16min
00: 224P
01: 288P
02: 0P
14: Auto regulation
00: 1°C
01: 2°C
02: 0.5°C
03: 1.5°C
04: 2.5°C
00: 1°C
01: 2°C
02: 0.5°C
03: 1.5°C
04: 2.5°C
00: 6°C
01: 2°C
02: 4°C
03: 8°C
04: 0°C

Advertisement

loading