3.3.7 Torque

Correct torque is imperative for all electrical connections.
The correct values are listed in Table 3.2. Incorrect torque
results in a bad electrical connection. Use a torque wrench
to ensure correct torque.
MG16N102
Operating Instructions
1
Enclosure
size
Danfoss A/S © 08/2015 All rights reserved.
2
308.3 [12.1]
253.1 [10.0]
180.3 [7.1]
3
.0 [.0]
44.40 [1.75]
244.40 [9.62]
Terminal
Torque [Nm] (in-
lbs)
Mains
19–40
Motor
(168–354)
D
Regen
8.5–20.5
Brake
(75–181)
Mains
19–40
Motor
(168–354)
E
Regen
8.5–20.5
Brake
(75–181)
Mains
19–40
Motor
(168–354)
8.5–20.5
F
Brake
(75–181)
8.5–20.5
Regen
(75–181)
Table 3.2 Torque for Terminals