6 Setup
Mode switch (1)
Sensitivity adjustment
(7, 8)
LED indication strip -
receive level (9)
Prerequisites
Mode
32
With the mode switch (min./max.) you can change the switching sta-
tus of the transistor output. You can set the required mode according
to the "Function table" (max. - max. detection or overflow protection,
min. - min. detection or dry run protection).
With these keys (7 and 8) you can adjust the switching point to the
medium.
Depending on the process, the sensitivity of VEGAMIP 62 must be set
higher or lower.
Pressing the "<--" key makes the sensor more sensitive. Pressing the
"-->" key makes the sensor less sensitive.
You can also adjust the switching delay with the two keys.
By means of the LED indicating strip, you can see the actual receive
level during adjustment.
When the indication moves to the right, the instrument is less sensi-
tive, to the left more sensitive.
6.2

Adjustment

The microwave barrier can only be adjusted when it is uncovered.
Make sure that no measured medium or vessel installations are
between the emitting and receiving unit.
Select the requested mode (min./max.) according to the function
table.
The following function table provides an overview of the switching
statuses depending on the set mode and level.
Level
Max. mode of op-
eration
Overflow protec-
tion
Max. mode of op-
eration
Overflow protec-
tion
Min. mode of op-
eration
Dry run protection
Min. mode of op-
eration
Dry run protection
Switching status Signal lamp
- Switching out-
put (yellow)
closed
open
closed
open
VEGAMIP R62 • Receiving unit