General Diagnosis - Daikin LX10F11B Service Manual

Inverter container refrigeration unit
Table of Contents

Advertisement

https://daikin-p.ru

2.7 General Diagnosis

If the unit does not work properly, refer to the following table for diagnosis to repair procedure and repair
action need.
Symptom
A. Compressor,
Faulty power
Evaporator fan,
supply
Condenser fan
dose not run.
Device malfunction Mega test check on secondary side
Controller
Secondary side
of power supply
transformer
B. Evaporator fan
Normal operation
runs, but condenser
(Cooling OFF
fan and compressor
status)
do not run.
C. Evaporator
Normal operation
fan and
<No action
compressor
needed>
run, but
condenser fan
does not run.
External factor
D. Condenser
Faulty electrical system
fan and
of evaporator fan
compressor
・CTP activation
run, but
・ Motor burnt out
evaporator fan
does not run.
・ Disconnected coil of
External factor
E. Compressor runs,
Normal operation
but evaporator fan
<No action
and condenser
needed>
fan do not run.
Cause
Voltage on primary side of circuit breaker
It should be within the voltage range
shown in paragraph 1-1.
of magnetic contactor (Evaporator fan
motor, condenser fan motor, compressor)
Unit switch ON/OFF check
Alarm presence (F code)
Check for disconnection of F2U (fuse)
Check for malfunction in object
models shown in paragraph 1.2.
Check for disconnection on secondary
side of transformer (Tr)
Check if there is AC24V between No.3
and 4 pins of connector X30A (I/O board).
Display of controller (ALARM display) See the alarm code
・ Check of operation of HPT (E101)
by controller display
・ Check if the condenser fan has
stopped during high-pressure control.
(Check that the condenser fan
operates at low speed at over 800kPa
and at high speed at over 1000kPa.)
Visual check debris and damage
(including relevant parts such as
controllers)
・Motor coil resistance
・ Ensure that the magnetic contactor
is turned ON
・ Voltage on secondary side of
(disconnection)
magnetic contactor (three-phase)
magnetic contactor
Visual check debris and damage
(including relevant parts such as
controllers)
・ Does "DEFROST" display on the
LCD panel?
・ Is the Defrost LED (orange)
illuminated?
Checkpoint
2-45
Remedy
Check the power supply
Check the power supply plug
Check for disconnection of cable
Replace faulty device.
Turn the switch ON.
See the instructions for
alarm code of controller
in paragraph 2.5.
Replace Fuse.
Replace faulty device.
Replace the transformer.
when ALARM is
generated
・ Refer to paragraph 2.6.
Depend on alarm
diagnosis
001
・ Normal if it operates at
low speed at over 800
kPa and at high speed
at over 1000 kPa.
repair as needed
・Replace the fan motor
・ Replace the magnetic
contactor
repair as needed