F401 ・ F405 ・ F407 ・ F409
Alarm
F401 SS, DSS, RS and DRS all failed during chilled mode, or X16A (CPU board) is disconnected.
Logic
F405 Multiple sensor (HPT,DCHS1,DCHS2) all failure.
and
F407 Multiple sensor (HPT,LPT) all failure.
Possible
F409 Multiple sensor (LPT,DCHS1,DCHS2) all failure.
Causes
Trouble
The unit cannot perform backup operation and cannot be controlled.
Shooting
Replace each failed sensor.
016
Refer to
,
Controller
F401, F405, F407, F409 Unit stop
Action
005
F701 ・ E701
Alarm
F701
Logic
① Abnormal power voltage is detected within 2 seconds when the unit starts. (≧AC565V or ≦
AC300V)
② One of R, S or T phase is open when the unit starts (F705 is also generated when S phase is
open.)
E701
③Abnormal power voltage is detected during operation. (≧AC565V or ≦AC329V)
④ One of R, S or T phase is open during operation (F705 is also generated when S phase is
open.)
Possible
Power supply voltage is at high voltage (≧AC565V) or low voltage (≦AC329V).
Causes
One of R,S,T phase is open
Trouble
①、③ Power check
Shooting
1. Check if the actual power supply within range (AC329V〜AC565V).
②、④ Check R,S,T phase is open
2.1 Check if there is open phase on the primary side
(Power side) of circuit breaker
2.2 Check if there is broken wire (open) on the secondary
side of circuit breaker
*Between CB〜X63A (PT/CT board)
Controller
F701 Unit stop
Action
E701  Restart after 3 minutes
017
019
, and
.
2.1 Repair or replace if there is a
problem in power plug or cable
Provide specified power supply
if there is open phase in power
supply
2.2 Repair as needed.