Humidity Set
OFF
▲▼:Change
ENTER:Confirm
<Optional Functions>
Defrost ending temperature setting
Bulb
Evap Fan Speed
Def
Temp
End
18.0℃
 ▲▼:Change
Confirm
ENTER:
Press
key to select the defrost
completion temperature in the range of 4.0℃
to 18.0℃ and press
※2-3 Humidity Set
1. Press
key to select
Humidity Setting and press
key to determine.
Humidity Setting:50〜95%RH
※2-4 USDA Set
1. Press
key to select number of sensors and press
4 sensors :4 USDA sensors connected
3 sensors :3 USDA sensors connected
AUTO
:Automatically recognize the number
 of USDA sensors connected (Note 1)
OFF
:No USDA sensor connected
Humidity Set
ENTER:Confirm
Humidity Set
ENTER:Confirm
Humidity Set
Evap Fan Speed
H-L
Def
End
 ▲▼:Change
ENTER:
key to determine.
Humidity Sepoint
95 % RH
▲▼ : Change
ENTER : Confirm
USDA
OFF
▲▼ : Change
ENTER : Confirm
ON
▲▼:Change
ON-A
▲▼:Change
Bulb
Press
key to select "L", "H-L," or "H" for
EFM speed and press
Bulb
H-L
Temp
15.0℃
Confirm
key to determine.
Note 1: To measure the temperature inside or cargo
temperature for the purposes other than cold
treatment transport, USDA sensor can record the
temperature ranging from –30.0 ℃ to +40 ℃ .
Do not use it for cold transport treatment
because it does not meet the USDA standards.
USDA
4 sensors
▲▼ : Change
ENTER : Confirm
2-7
Mode Set screen
EFM speed setting
Bulb
Evap Fan Speed
L
Def End Temp
18. . 0℃
▲▼:Change
ENTER:Confirm
key to determine.
Mode Set display
Humidity Setpoint
75 % RH
▲▼ : Change
ENTER : Confirm