4.9.4 Fixing of DMV Opening

For the emergency operation when controller or
DMV coil is malfunctioned, fix DMV opening fully
using emergency magnet.
Preparation : Emergency magnet Parts
No.1896110.
① Disconnect connector X11A(Blue) on CPU
board.(To de-energized to DMV coil)
Refer the location of X11A to CPU board, in
paragraph 1.3.4.
②Remove fixing plate and DMV coil.
③ Bring the emergency magnet into contact with
valve head, turn the magnet clockwise to open
fully. There is a small click sound when the valve
is fully opened.
(Approximate 10 turns from full close to full
open.)
④Install coil and fixing plate.
Valve head
Fixing plate
Valve body
ATTENTION !!
Make sure to reconnect connector X11A (Blue)
to the socket on CPU board when the operation
returns to normal.
Coil
②Full open
Upside
Emergency magnet
(Yellow label)
4-26