Daikin LX10F11B Service Manual page 49

Inverter container refrigeration unit
Table of Contents

Advertisement

https://daikin-p.ru
●Inverter F Alarm
Alarm
Diagnosis
code
101
F528
E528 (Compressor does not startup) is generated 5 times.
102
F52E
E52E (Temporary compressor overcurrent ) is generated 4 times.
102
F52F
E52F (Compressor current sensor failure) is generated 4 times.
103
F536
E536 (Current sensor offset error) is generated 4 times.
103
F538
Inverter board failure (Microcomputer I/O port logic judgment
failure when unit is on)
104
F53A
Incorrect setting (Controller model)
102
F53B
Inverter board failure (EEPROM fault when unit is on)
103
F53C
E53C (Main circuit condenser recharging error) is generated 4 times. UNIT stops
101
F53D
E53D (Compressor lock) is generated 4 times.
●Inverter E Alarm
Alarm
Diagnosis
code
101
E523
Compressor over current (>16.1A) is detected during operation.
101
E524
Compressor over current (>19A) is detected during operation.
101
E525
Actual frequency much lower than command frequency due to
compressor over load
105
E526
Actual frequency much higher than command frequency due to
external factors
101
E528
Compressor does not operate after startup.
106
E52C
Inverter board temperature higher than 99 ℃
102
E52D
Inverter board temperature abnormal (> 150 ℃ or < -45 ℃ is
detected.)
102
E52E
Current is too high temporary during startup (over 51A)
102
E52F
Compressor current sensor failure at startup
107
E531
Power supply voltage is unbalance
108
E532
Power supply voltage error (too high, too low at abnormally)
109
E533
Power supply voltage error (open phase)
103
E536
Current sensor offset fault when compressor starts
103
E53C
Main circuit charge failure when compressor starts
101
E53D
Compressor lock when compressor starts
110
E542
Cooling fan lock during operation (LX10F15A only)
111
E5FF
A communication error between CPU board (EC1) and Inverter
board (EC8)
Alarm content
Alarm content
2-21
Controller action
UNIT stops
UNIT stops
UNIT stops
UNIT stops
UNIT stops
UNIT stops
UNIT stops
UNIT stops
Controller action
Restart after 3 min.
Restart after 3 min.
Restart after 3 min.
Restart after 3 min.
Restart after 3 min.
Restart after 3 min.
Restart after 3 min.
Restart after 3 min.
Restart after 3 min.
Restart after 3 min.
Restart after 3 min.
Restart after 3 min.
Restart after 3 min.
Restart after 3 min.
Restart after 3 min.
Alarm display only
Restart after 3 min.