2.5 Alarm Code

●Alarm grouping
F---:Alarm that unit stop
E---:Alarm that unit restart or backup operation
T---:Alarm during PTI (Refer to paragraph 3.3.2.)
F5---:Alarm that unit stop related to inverter
E5---:Alarm that unit restart related to inverter
Communication Interrupted: Communication error between CPU board (EC1) and
operation board (EC3)
Alarm
Critical shut down.
F ---
(Requires inspection/repair)
The unit stops, but restarts 3 minutes after the condition returns to normal.
If the same error occurs multiple times, the unit will switch to standby for 4 hours or stop.
E ---
Unit continues operation by back-up operation.
Alarm display only. Unit continues operation.
Alarm LED and Alarm Code Display
Alarm
Alarm LED (Red)
F Alarm,
E807, E304
E Alarm
●F Alarm
Alarm
Diagnosis
code
001
F101
HPS activates within 30 seconds after compressor starts.
(2400 kPa or more)
002
F109
LPT drops below -72kPa within 2 seconds after compressor starts
003
F301
Temperature setting request
004
F401
SS, DSS, RS and DRS all failed in chilled mode
004
F405
HPT, DCHS1 and DCHS2 all failed
004
F407
HPT and LPT both failed
004
F409
LPT, DCHS1 and DCHS2 all failed
005
F701
Abnormal power supply voltage detected within 2 seconds after
unit turns on
One of R, S or T phase is open after unit turns on
006
F703
Unbalance power supply
007
F705
Open power phase during operation
008
F707
Fuse F2U is open (I/O board)
009
F809
E809 (shortage of refrigerant) is generated twice
Controller action at the generating of alarm
Blinking
Press
OFF
Alarm content
Alarm code display
or
key to display alarm code.
2-19
Controller action
UNIT stops
UNIT stops
UNIT stops
UNIT stops
UNIT stops
UNIT stops
UNIT stops
UNIT stops
UNIT stops
UNIT stops
UNIT stops
UNIT stops