5. To confirm that the sensors have been configured successfully go to the "Monitor" tab under "D-Wire 1-8" or
"D-Wire 9-16" tab. (depending on which sensors you have configured) Sensors configured successfully will
appear in the list normally. (not outlined)
Removing damaged sensor and replacing with new sensor:
1. Remove damaged sensor from unit and replace with new sensor. In the "Monitor" tab under "D-Wire 1-8" or
"D-Wire 9-16" (depending on which sensor is damaged and being replaced) the damaged/removed sensors will
show highlighted.
2. To delete the damaged sensors from the list, go to the "EDIT" tab under "D-Wire 1-8" or "D-Wire 9-
16" (depending on the sensor being replaced) and delete the sensor descriptions of the sensors that have been

Advertisement