13.3.6.8
TCP Paging Setup
Heading
MSG_BEG
Sequential message number used to group the message and detect missing
MSG_END
messages (e.g. 00001, 00002, etc...).
VID
Vendor ID
FID
NetGuardian Firmware ID.
SITE
NetGuardian system name.
PNT
Point ID (port.address.display.point). See Appendix A for display mapping.
DESC
Description set forth in the Alarm parameters.
STAT
Status of the alarm (Clear or Alarm).
DATE
Date the alarm occurred.
TIME
Time the alarm occurred.
The NetGuardian offers alarm status notification via multiple TCP ports. When an alarm condition occurs, an
alarm condition formatted according to Figure 2.17 will be sent to the specified TCP points for use by a higher
level master. This connection must be established by the master. Any applicable alarm activity occurring prior to
an established connection will be discarded.
Use the following steps to configure the TCP paging settings:
1. Under the
column, select
Type
2. In the
Pin/Rcpt/Port
1 to 65,536). Multiple ports can be defined by defining multiple pager IDs as TCP pagers and then entering the
desired ports.
3. The TCP message can be viewed by a Telnet session by connecting to the NetGuardian's IP address and the
TCP port entered in this screen. For example, Telnet to
126.10.220.199 is the unit's IP address. See Figure 2.17 for an example message and Table 2.H for TCP
message format information.
13.3.6.9
NUM17 Pager Setup
The Num17 Pager can receive point addresses of alarms. It is quite similar to the Numeric Paging format in the
way it receives and reports alarms. However, on certain pager systems the symbol * will cause a freeze or other
undesirable situations. Num17 eliminates the * symbol from the pages it receives and reports alarms as a 17-digit
series of numbers.
<MSG_BEG 00001>
VID : DPS Telecom
FID : NetGuardian SNMP v5.0B.3206
SITE: Yale Office
PNT : 99.01.01.01
DESC: RECTIFIER 1
STAT: CLEAR
DATE: 01/01/2001
TIME: 12:17:02
<MSG_END 00001>
Fig. 2.17. Example TCP message
Table 2.H. TCP alarm message field descriptions
from the drop-down menu.
TCP
field enter the NetGuardian TCP port number where alarm messages will be sent (from
Description
if port 5000 is selected and
126.10.220.199 5000
63
Need help?
Do you have a question about the NetGuardian 420 DNP3 and is the answer not in the manual?
Questions and answers