Troubleshooting - Gira 2114 00 Operating Instructions Manual

Heating actuator basic, 6-gang
Table of Contents

Advertisement

Heating actuator basic, 6-gang
Rated voltage KNX
Power consumption KNX
Power loss
Heating outputs
Contact type
Switching voltage
Mains frequency
Switching current
Switch-on current
Switch-on current
Number of drives per output
230 V drives
24 V drives
Housing
Installation width
Connection of outputs
Connection mode
Single stranded
Finely stranded without conductor sleeve
Finely stranded with conductor sleeve
6

Troubleshooting

Valve drives of an output or all outputs do not switch
Cause: An output is overloaded.
Determine cause of the overload switch-off. Eliminate short-circuits, replace de-
fective valve drives. Check number of valve drives connected to the output, re-
duce if necessary. Do not exceed max. switching current.
Reset overload switch-off: disconnect device from mains completely for approx.
5 seconds, switch off miniature circuit-breaker. Then switch on again.
In case of overload, initially one or both output groups switch off for approx.
6 minutes. After that the device determines which output is overloaded and
switches it off permanently. This rest and test phase lasts 6 to 20 minutes.
After resetting of the overload switch-off it is no longer possible for the device
to determine which output is overloaded. If the cause is not eliminated, over-
load switch-off will occur again.
32590712
10870571
22.03.2023
DC 21 ... 32 V SELV
max. 250 mW
max. 1 W
Semi-conductor (Triac), ε
AC 24 / 230 V ~
50 / 60 Hz
5 ... 160 mA
max. 1.5 A (2 s)
max. 0.3 A (2 min)
max. 4
max. 2
72 mm / 4 HP
Screw terminal
0.5 ... 4 mm²
0.5 ... 4 mm²
0.5 ... 2.5 mm²
8 / 9