Unipulse F160 Operation Manual page 92

Weighing controller
Table of Contents

Advertisement

Code
30
Digital filter
31
Motion detection (period)
32
Motion detection (range)
33
Zero tracking (period)
34
Zero tracking (range)
35
Analog filter
36
Filter in a stable condition
37
Motion detection mode
38
Option setting
39
SI/F G/N selection
Code
40
Balance weight
41
Capacity
42
Minimum scale division
43
Net over
44
Gross over
45
Digital zero regulation value
46
Decimal place
47
Gravitational acceleration
48
Calibration value LOCK
49
Set value LOCK
83
Function
0000 (OFF), 0002 to 1024 [times]
0.0 to 9.9
00 to 99
0.0 to 9.9
00 to 99
0: 2, 1: 4, 2: 6, 3: 8 [Hz]
0: Insert (256times), 1: Not insert
0: Stable mode, 1: Checker mode
No option
BCD Parallel Data Output Interface
CC-Link Interface
0: Gross weight, 1: Net weight
Function
00000 to 99999
00000 to 99999
001 to 100
00000 to 99999
00000 to 99999
0000 to 9999
0: 0, 1: 0.0, 2: 0.00, 3: 0.000
01 to 16
0: Release, 1: LOCK
0: Release, 1: LOCK
Setting range
0 0 0 0 0
Undefined
0 3 0 1 0
Undefined
Output signal selection
0: Near zero, 1: Stable, 2: Weight alarm,
3: Sequence error, 4: Final error,
5: Zero alarm
BCD output data form
0: BCD, 1: Binary
BCD output rate [Times/sec.]
0: 10, 1: 20, 2: 50, 3: 100,
4: 200, 5: 500, 6: 1000
BCD output data selection
0: Gross weight, 1: Net weight,
2: Tare weight, 3: Ext.
4 0 1 0 0
Undefined
Station No.
1 to 63
Baud rate [bps]
0: 156k, 1: 625k, 2: 2.5M, 3: 5M, 4: 10M
Setting range
9 SUPPLEMENTS
83
Chapter
9

Advertisement

Table of Contents
loading

Table of Contents