4.3

Installation positions and minimum distances

4.3.1

Minimum distances for ensuring installability

Note the dimensions shown in the following diagram for the design of the signal distribution board to ensure
safe latching and simple assembly / disassembly of the modules.
Fig. 18: Mounting distances EJ module - PCB
Observing the reaching area
A minimum reaching area of 92 mm is required for assembly / disassembly, in order to be able to
reach the mounting tabs with the fingers.
Adherence to the recommended minimum distances for ventilation (see section Installation position
[} 32]) ensures an adequate reaching area.
The signal distribution board must have a thickness of 1.6 mm and a minimum distance of 4 mm from the
mounting surface, in order to ensure latching of the modules on the board.
EJ18xx
Version: 1.5
Installation of EJ modules
31