5.4.7 Permissible grid voltages

3P3W
Voltage Range
L1-L2
400 V
-20%/+30%
AC
L1-L3
400 V
-20%/+30%
AC
L2-L3
400 V
-20%/+30%
AC

5.4.8 Selecting the AC cable

5.4.8.1 Technical properties of the AC terminal block
Connection type
Rated current I
N
Rated voltage U
N
Type of attachment
Tightening torque
Table 5.1.: Technical specification for the AC terminal block
180 mm
Fig. 5.17:
Free space for wiring on the AC terminal block
5.4.8.2 Notes on calculating the cable cross-section
► Consider the following factors when calculating the cable
cross-section:
Cable material
Temperature conditions
Cable length
Installation type
Voltage drop
Loss of power in the cable
► Always follow the IEC 60364-5-52 requirements and your
country-specific installation instructions.
► France: Follow the installation instructions of UTE 15-712-
1. This standard contains the requirements for minimum
cable diameters and for avoiding overheating due to high
currents.
Installation and Operation Manual M50A_260 RPI503M260000 Product version L and M EU V1.3 EN 2023-08-14
3P4W Voltage Range
L1-N
230 V
-20%/+30%
AC
L2-N
230 V
-20%/+30%
AC
L3-N
230 V
-20%/+30%
AC
Screws with hexagon socket head
96 A
1000 V
4.5 mm hexagon socket (L1,
L2, L3, N)
M8 nut (PE)
12.4 Nm (L1, L2, L3, N)
14.7 Nm (PE)
5 Planning the installation
Planning the grid connection (AC)
► Germany: Follow the installation instructions of VDE 0100-
712. This standard contains the requirements for minimum
cable diameters and for avoiding overheating due to high
currents.
5.4.8.3 Specifications for copper AC cables
Min./max. Cable diameter
Min./max. Wire cross section
Without wire end sleeve
Rigid cable
Multi-wire cable
With wire end sleeve
Flexible cable
Table 5.2.: Specifications for copper AC cables
5.4.8.4 Specifications for aluminum AC cables
Min./max. Cable diameter
Min./max. Wire cross section
Without wire end sleeve
round, single-wire (rs)
round, multi-wire (rm)
sector-shaped (ss)
1)
1) Observe the installation instructions for the use of sector-shaped aluminum
cables (see section 5.4.8.7, p. 40)
Table 5.3.: Specifications for aluminum AC cables
5.4.8.5 Stripping length
20 mm
20 mm
Fig. 5.18:
Stripping length for AC cables
5.4.8.6 Handling aluminum conductors during installation
work
► The special properties of aluminum must be taken into con-
sideration when using aluminum conductors:
Aluminum "flows," i.e. it gives way under pressure.
A thin non-conductive oxide layer forms within a few
minutes on de-insulation, which increases the contact
resistance between the conductor and clamping point.
The specific conductivity and hence the current carry-
ing capacity is approximately one third less than that of
copper.
21,9 to 44,7 mm
2
25 to 60 mm
25 to 60 mm
2
2
25 to 60 mm
21,9 to 44,7 mm
2
35 to 60 mm
35 to 60 mm
2
35 to 60 mm
2
39