Important information for system operators
WARNING Health hazard from chemical substances.
Some states list chemical substances known to cause cancer, birth defects, death, serious illness, or other
reproductive harm in propositions. This product may contain such substances, either from the fuel, fuel com-
bustion, or in components of the product itself.
WARNING Necessary tasks.
The heat exchanger, flue pipe, and chimney must be cleaned regularly to remove accumulated creosote and
ash. Ensure that the heat exchanger, flue pipe, and chimney are cleaned at the end of each heating season
to minimize corrosion during the summer months. The appliance, flue pipe, and chimney must be in good
condition. These instructions also apply to a draft inducer, if used.
WARNING Pellet feed system: service, maintenance and rules
The pellet feed system operates automatically. All service and maintenance must be completed by trained
specialists only. Do not alter the equipment or accessories in any way.
For use in combination with Windhager BioWIN 2 Touch pellet-fueled central heating boiler/furnace only.
Do not use to transport any material other than wood pellet fuel listed on the boiler nameplate or in the boiler
manuals.
Do not use for vacuum cleaning.
The pellet feed system starts automatically and will make noise. People who are easily startled or have car-
diac problems should keep away.
DANGER Pellet feed unit: Risk of fire or explosion.
Can lead to serious injury/death! Ground suction hoses must be installed as described in the installation
manual at every connection to avoid static sparking/dust ignition. The pellet feed unit is for use with the day
hopper only. The feed unit must be braced, anchored, or strapped to avoid falling/shifting during an earth-
quake. Instructions can be obtained from your local Windhager dealer or wholesaler.
Pellet feed automatic changeover unit: Fire and explosion hazard
Fire and explosion hazard can lead to serious injury or death.
Do not use the pellet feed automatic changeover unit inside pellet storage room or where there is a lot of
dust present. Connect delivery hoses to pellet feed automatic changeover unit as described in the installation
manual to avoid static sparking or dust ignition.
WARNING Pellet feed automatic changeover unit: injury hazard by moving
parts and electricity
Can lead to serious injury or death.
Device starts automatically. Device restarts automatically after power failure.
Do not remove cover.
This part should be serviced by trained personnel only.
WARNING Clearances and installation instructions
Minimum clearances from combustible or noncombustible construction:
2 inches left, 12 inches back, 24 inches top (right),
6 inches right side, 22 inches front.
Access to the back side is required to allow the service of parts such as the drain valve, relief valve, and
inspection fittings.
This unit is for dry indoor installation only. Not for installation on combustible flooring. Not for installation
in manufactured homes or mobile homes.