I/O Signal When Cc-Link Ver.2 Octuple Setting Is Selected (Pr.544 = 18, 28) - Mitsubishi Electric FR-A8NC Instruction Manual

Hide thumbs Also See for FR-A8NC:
Table of Contents

Advertisement

6.2.5

I/O signal when CC-Link Ver.2 octuple setting is selected (Pr.544 = 18, 28)

 Remote I/O (32 points (128 points occupied))
Same as when Pr.544 = 0 (Refer to
 Remote register
*4
Address
Upper 8 bits
RWwn
Monitor code 2
RWwn+1
Set frequency (0.01 Hz increments)
Link parameter
RWwn+2
extended setting
RWwn+3
Write data
RWwn+4
Monitor code 3
RWwn+5
Monitor code 4
RWwn+6
Monitor code 5
RWwn+7
Monitor code 6
RWwn+8
Fault history No.
RWwn+9
PID set point (0.01% increments)
RWwn+A
PID measured value (0.01% increments)
RWwn+B
PID deviation (0.01% increments)
Torque command or torque limit
RWwn+C
Torque command or torque limit (1st
*3
quadrant)
*2
RWwn+D
H00 (Free)
/ Torque limit (2nd quadrant)
*3
RWwn+E
H00 (Free)
/ Torque limit (3rd quadrant)
*2
RWwn+F
H00 (Free)
/ Torque limit (4th quadrant)
page
54)
Description
Lower 8 bits
Monitor code 1
Instruction code
68
H00
*1
*1
*1
*2
/
68,
*3
*3
68
*3
Refer
*4
to
Address
Upper 8 bits
page
RWrn
First monitor value
RWrn+1
Second monitor value
RWrn+2
Reply code 2
RWrn+3
Read data
RWrn+4
Third monitor value
RWrn+5
Fourth monitor value
RWrn+6
Fifth monitor value
RWrn+7
Sixth monitor value
RWrn+8
Fault history No.
RWrn+9
Fault record (output frequency)
RWrn+A
Fault record (output current)
RWrn+B
Fault record (output voltage)
80
RWrn+C
Fault record (energization time)
RWrn+D
RWrn+E
H00 (Free)
RWrn+F
Description
Refer
Lower 8 bits
page
Reply code 1
71
Fault history data
I/O SIGNAL LIST
to
6
61

Advertisement

Table of Contents
loading

Table of Contents