Mitsubishi Electric FR-A8NC Instruction Manual page 68

Hide thumbs Also See for FR-A8NC:
Table of Contents

Advertisement

Device no.
Frequency setting completion/torque
RXE
command setting completion
(RAM, EEPROM)
RXF
Instruction code execution completion
RX1A
Error status flag
RX1B
Remote station ready
*1
Signal names are initial values. Using Pr.190 to Pr.196, you can change output signal functions.
Refer to the Instruction Manual (Detailed) of the inverter for details of Pr.190 to Pr.196.
*2
Signals are not assigned in the initial setting. Use Pr.313 to Pr.315 to assign signals to the devices RX9 to RXB.
The settings of Pr.313 to Pr.315 are the same as those of Pr.190 to Pr.196 (output terminal function selection).
Refer to the Instruction Manual (Detailed) of the inverter for details of Pr.313 to Pr.315.
*3
The torque command setting is available only for the FR-A800 series.
Signal
After "1" is set in the frequency setting command/torque command (RYE)
and the frequency setting command/torque command is written to the
*3
inverter RAM and EEPROM, "1" is set in this signal.
When "0" is set in the frequency setting command/torque command (RYE),
"0" is set in this signal.
After "1" is set in the instruction code execution request (RYF) and the
processes corresponding to the instruction codes (RWw2, 10, 12, 14, 16
and 18) are executed, "1" is set in this signal.
When "0" is set in the instruction code execution request (RYF), "0" is set in
this signal.
When an inverter error occurs (protective function is activated), "1" is set in
this signal.
When the inverter goes into the ready status upon completion of initial
setting after power-on or hardware reset, "1" is set in this signal. When an
inverter error occurs (protective function is activated), "0" is set in this
signal.
The signal is used as an interlock signal during the write to/read from the
master module.
Description
DETAILS OF INPUT AND OUTPUT SIGNALS
7
67