Monitor Codes - Mitsubishi Electric FR-A8NC Instruction Manual

Hide thumbs Also See for FR-A8NC:
Table of Contents

Advertisement

7.2.4

Monitor codes

Information about the inverter can be monitored by setting the special monitor selection No. of the instruction code and monitor
code using the remote registers, RWw0 and RWw4 to 7.
• For the monitor code (RWw0), select the first monitor description (RWr0) from the lower 8 bits and the second monitor
description (RWr1) from the upper 8 bits.
Ex.
When output current is selected for the first monitor (RWr0) and running speed is selected for the second monitor (RWr1) 
monitor code (RWw0) is H0602
• When Pr.544 = "12, 14, or 18", descriptions of monitor codes 3 (RWw4) to 6 (RWw7) can be selected.
Second monitor
Monitor code
description
(the first 8 bits)
H00
Output frequency
H01
Output frequency
H02
Output current
H03
Output voltage
.
.
.
.
.
.
NOTE
• The monitor codes (monitored items) after H01 are the same as those of the RS-485 communication dedicated monitor. For
the details of the monitor code and monitor description, refer to the section of the monitor display in the Instruction Manual
(Detailed) of the inverter.
• When the remote registers RWw0 and RWw4 to 7 are used for monitoring, H00 (output frequency), H01 (output frequency),
and H05 (set frequency) always indicate the frequency regardless of the settings of Pr.37, Pr.144, and Pr.811. (Pr.811 is
only available for the FR-A800 series.)
First, third to sixth monitor
description
(the last 8 bits)
No monitoring (monitor value is 0)
DETAILS OF INPUT AND OUTPUT SIGNALS
Increments
0.01 Hz
0.01 Hz
0.01 A/0.1 A
0.1 V
.
.
.
7
79

Advertisement

Table of Contents
loading

Table of Contents