Mitsubishi Electric FR-A8NC Instruction Manual page 74

Hide thumbs Also See for FR-A8NC:
Table of Contents

Advertisement

 Reply code definition
The reply to the instruction execution is set to RWr2, 10, 12, 14, 16, 18.
When executing the frequency setting (RYD, RYE) or instruction code execution (RYF), check the reply code (RWr2) in the
remote register after execution.
Data
H0000
Normal
H0001
Write mode error
Reply
code
Parameter selection
H0002
error
H0003
Setting range error
H00
Normal
H01
Write mode error
Reply
*1
code 1
Frequency command /
torque command /
H03
torque limit setting
range error
H00
Normal
H01
Write mode error
Reply
code 2
Parameter selection
H02
error
H03
Setting range error
Item
No error (normal completion of instruction code
execution)
Parameter write was attempted during operation
other than a stop in the network operation mode.
Unregistered code number was set.
Set data is outside the permissible data range.
No error (normal completion of instruction code
execution)
Parameter write was attempted during operation
other than a stop in the network operation mode.
The value outside the range is set.
No error (normal completion of instruction code
execution)
Parameter write was attempted during operation
other than a stop in the network operation mode.
Unregistered code number was set.
Set data is outside the permissible data range.
Alarm definition
DETAILS OF INPUT AND OUTPUT SIGNALS
Remarks
• Reply code to RWr2 when
Pr.544 = 0
• Reply code to RWw10, 12, 14,
16, and 18 when Pr.544 = 18
Reply code to RWr2 when Pr.544
 0
7
73