Note:
If the doors are commanded by the controller this value must be set to "Ignore" (Value 0)
Menu
Par
Description
5.7.7
11212
Door hold off
Setting of delay from signaling of Door fbk fail alarm condition and tripping of alarm. If an alarm condition occurs, the
drive waits for the set time to elapse before tripping the alarm. If the alarm condition is eliminated within the time set in
this parameter, the drive does not trip the alarm.
Menu
Par
Description
5.7.8
11268
Reset Brake Alarm
This command is the reset of the Brake Alarm. Reset procedure:
1. On menu 5.9 LIFT ALARMS,, check if the
2. Enter PAR 11268 Reset Brake Alarm (default 0).
3. The system requests a code to cancel the alarm: enter 5313.
4. On menu 5.9 LIFT ALARMS,, check that the Brake Alarm parameter is OFF.
ADL300 CiA® 417- Description of functions and parameter list
UM
Type
FB BIT
ms
INT16
UM
Type
FB BIT
SHORT
Brake Alarm
parameter is ON.
Def
Min
Max
1000
0
60000
Def
Min
Max
0
Acc
Mod
RW
FVS
Acc
Mod
RW
FVS
Page 42 of 46