05.03 – SEQUENCES
This menu describes the parameters used to manage and set lift travel based on the status of inputs and alarms. The
following section summarizes the structure of lift sequences in case of floor call command. After the command is
received and the number of the destination floor is saved, the internal positioner starts, which automatically runs the
trajectory until the destination floor is reached with direct arrival.
In case of Jog running, the deceleration sequence starts when the jog command ends.
Start sequence:
1 Reading of Enable hardware input and checking of presence of alarms (in case of alarm, the enable is interrupted)
2 Master command read as set as B0
3 After time set in Cont close delay has lapsed, internal Enable signal is activated and the start speed set as B1 is
communicated to drive.
4 Wait for Magn. current (Drive ready) signal from drive
5 At end of magnetization, brake open signal is activated
6 Wait for (Brake open delay) time.
7 After brake open delay time has lapsed, Start lift is commanded and movement is enabled.
Sequence of movement:
1 The motor starts with the values shown on the ramp. Movement follows multispeed and the "S" ramp set in internal
position control.
2 When the set speed is exceeded, you can check that the brake has actually opened with the Brake 2 mon output
signal.
3 Internal position control follows the set trajectory and starts the deceleration ramp at the appropriate time.
ADL300 CiA® 417- Description of functions and parameter list