Synchrocheck With regard to closing the interconnection switch, the Ekip Synchrocheck module recognizes and reports
Programmable Functions and
Commands
84 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
whether there are synchronism conditions between two independent voltage sources (example: generator
+ grid).
A description of the module, the protection function and performance is given in the chapter dedicated to
the modules (page 174).
Eight commands are available, with activation that can be programmed on the basis of signals or events.
Distributed among different Ekip Touch menus, the commands are:
Name
Description
External Trip
Sends a TRIP command
Trip RESET
Reset of the trip signal
Turn on SET B
Changes the protections set, from Set A to Set B
It activates 2I protection, if configured for this
2I Mode
function
RESET Energy
Resets the energy meters
YO Command
Sends an open command to YO
YC Command
Sends a close command to YC
LOCAL Switch On
Changes the configuration, from Remote to Local
Signaling RESET
Reset the contacts of the signalling modules
(1)
the MOE-E storage command must be present
Parameters
Each command provides two programming parameters:
Parameter
Description
Event or several command activation events (up to eight, in AND
Function
or OR logic configuration). The Custom configuration can be
programmed via Ekip Connect.
This is the minimum time the expected event must be present in order
Delay
to activate the command; the value is given in seconds and can be set
within a range: 0 s to 100 s, in 0.1 s steps
IMPORTANT: the commands are sent if all the operating conditions expected by the
unit are present (connections, power supplies, alarms, etc.)
Path (page)
Advanced - Functions (35)
Advanced - Functions - 2I
Menu (50)
Measurements - Energy (36)
Settings - Functions (37)
(1)
Settings - Modules
-Functions (37)
Protections | 15 - Additional protections and functions
ABB | SACE Tmax XT
Default
Deactivated
0 s