Protections - ABB SACE Tmax XT7 Operation And Maintenance Manual

For ekip touch trip units, tmax low voltage moulded-case circuit-breakers xt7
Hide thumbs Also See for SACE Tmax XT7:
Table of Contents

Advertisement

Protections

Operating principle The protection functions are available with all Ekip Touch models and versions.
References Many of the protection thresholds are displayed in two different quantities: absolute value and relative value.
Protections packages The protections described in the following chapters are grouped into packages, the availability of which
42 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Each protection is associated with a different signal (current, voltages, frequencies, powers, etc) but the
operating principle is the same:
1.
If the signal measured exceeds the set threshold, the specific protection activates (prealarm and/or
alarm).
2.
The alarm appears on the display and, after a period of time (timing t
parameters set, can convert into a trip command (TRIP) transmitted to the internal Trip coil of the
CB.
NOTE:
• if the signal measured drops below the set threshold before the trip time has elapsed, Ekip
Touch quits the alarm and/or timing status and returns to the normal operating condition
• all protections have a default configuration: check the parameters and change to suit the
installation requirements before putting into service
TRIP When the Ekip CI module is present, Ekip M Touch allows a different TRIP configuration to be selected so
that, if a trip occurs, a contact of the Ekip CI module connected to an external remote control switch is
commanded (Normal mode).
NOTE: TRIP is always controlled by a command to the Trip Coil for protections I and G
Consult the parameters used with Ekip Touch MLRIU for further details (page 130).
The relative value depends on the type of measurement:
Type of protection
Current
Voltage
Frequency
Power
depends on the model and version of the Trip unit, and on their ability to be installed as additional package:
Package
Standard Protections
Voltage protections
Voltage Advanced protections
Frequency protections
Power protections
Adaptive protections
Motor protections
Reference
Description
In
Nominal current of the Rating plug
Un
Line-to-line voltage setting
fn
Frequency setting
√3 x In x Un
Sn
Page
43
53
56
60
63
70
71
ABB | SACE Tmax XT
), depending on the protection
t
Protections | 6 - PIN and security

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents