ABB SACE Tmax XT7 Operation And Maintenance Manual page 184

For ekip touch trip units, tmax low voltage moulded-case circuit-breakers xt7
Hide thumbs Also See for SACE Tmax XT7:
Table of Contents

Advertisement

Alarm signals Up to three alarm thresholds (independent of each other), Threshold A, Threshold B, Threshold C, can be
States and alarms The state of all control thresholds can be checked in the Warnings/Alarms page
182 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
activated and configured for each input in the Protection parameters - Other parameters A (and B if dual set
is activated) page
Each alarm threshold has the following configuration parameters:
NOTE: the table lists the parameters of threshold A of input I42; the names and references
of all the other thresholds and inputs change
Parameter
Description
Threshold A enable Activates verification of input I42 with alarm Threshold A
Defines whether the alarm must activate when measurement is above
Threshold A
(Up) or below (Down) the set value, with reference to the Threshold A
hysteresis direction
setting
Alarm threshold A of input I42. The value is given in degrees Celsius
(°C) and can be set within the range: -40°C to 240°C, in 0.1°C steps.
NOTE: the thresholds of the 4-20mA (I41 and I51) Current Loop
Threshold A value
input are given in percentage form and can be set within the
range: 0% to 100 %, in 0.1% steps (each step equivalent to
0.016µA)
Hysteresis value, valid for quitting the alarm condition if the set Treshold
A alarm threshold has been exceeded.
The hysteresis parameter only allows positive values. The trip unit
decides whether to add or subtract this value to or from the alarm
threshold on the basis of the direction parameter, example:
• Direction = Up, Value = 200°C, hysteresis= 10°C, the alarm activates
Threshold A
over 200° and de-activates below 190°C
hysteresis
The value is expressed in degrees Celsius (°C) and can be set within
the range: 0°C to 50°C with 0.1°C steps.
NOTE: the thresholds associated with the 4-20mA (I41 and I51)
Current Loop input are given in percentage form and can be set
within the range 0% to 30 %, in 0.1% steps (each step equivalent
to 0.016µA)
ABB | SACE Tmax XT
External electronic accessories | 13 - Ekip Signalling 3T
Default
Off
Up
200 °C (I42,
I43, I44,
I52, I53,
I54) / 50 %
(I41, I51)
1 °C (I42,
I43, I44,
I52, I53,
I54) / 1 %
(I41, I51)