ABB SACE Tmax XT7 Operation And Maintenance Manual page 131

For ekip touch trip units, tmax low voltage moulded-case circuit-breakers xt7
Hide thumbs Also See for SACE Tmax XT7:
Table of Contents

Advertisement

Test Bus The parameter allows parameter editing via the service connector to be enabled/disabled, thereby limiting
Maintenance The parameter allows an alarm, concerning maintenance of the unit, to be enabled/disabled. (page 112).
129 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
the possibility of configuring all the options on the display (in the Local mode) or via modules Ekip Com (in
the Remote mode).
Disabling the parameter, Local mode and using the PIN allow security against undesired modification by
unauthorized persons to be increased.
NOTE: with Test Bus= Off, communication via service connector is still guaranteed (reading
enabled)
Ekip Touch is supplied with the parameter set to: On.
System The System menu provides various options:
Parameter
Date
Time
Language
PIN
IMPORTANT: setting and checking Date and Time is important for all the recording
functions (trips or measurements); in the event of date and time glitches, reset
and if necessary replace the battery inside Ekip Touch (page 19).
View The View menu provides various options:
Parameter
TFT orientation
Customer page
Ammeter Phase
Voltmeter Phase
Ekip Touch is supplied with the parameter set to: On.
Description
Setting the current date
Setting the current time
Setting the language in display menus
PIN setting (page 41)
Description
Enables the orientation of the Alarms List, Measuring Instruments and
Main Measurements pages to be set. The options are: Horizontal, Vertical
clockwise, Vertical counter-clockwise
Allows you to activate a supplementary information page, which can
be accessed by pressing the iTEST button twice from any page with a
diagnosis bar. The information on the new page can be configured via Ekip
Connect (page 132)
Allows the current to be displayed in the Measuring instruments page to be
set from among the following options: Imax, I1, I2, I3, Ne (only in the 4P or
3P + N configuration)
Allows the voltage to be displayed in the Measuring instruments page to be
set from among the following options: Vmax, V12, V23, V31
ABB | SACE Tmax XT
Default
English
00001
Default
Horizontal
Off
Imax
Vmax
Ekip Touch - Settings | 1 - Main settings