ABB SACE Tmax XT7 Operation And Maintenance Manual page 167

For ekip touch trip units, tmax low voltage moulded-case circuit-breakers xt7
Hide thumbs Also See for SACE Tmax XT7:
Table of Contents

Advertisement

Remote Link configurations Regarding the Link functions, the following further parameters are available:
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
Remote Link information Regarding the Link functions, the following further parameters are available:
165 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Continued from the previous page
Parameter
Description
Permits (Enabled ARP) the periodic generation of a Gratuituos
ARP message, used by Ekip Connect to rapidly find the
Disable Gratuitous ARP
modules via Ethernet scan without knowing the IP address
beforehand
Password protected
Enables the writing operations performed via the network to be
protected by a password (Request password)
access
With access protected by enabled password, this is the
Password Modbus TCP
password to use before each writing session
(1)
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
(2)
the parameter can only be changed via system bus in the remote configuration
Parameter
Description
Link Actor (1÷15)
IP address of each actor (from 1 to 15)
Configuration parameters of the configurable states:
• selection of actor (actor from 1 to 15) which activates the
Remote Programmable
programmable status
Status (A÷D)
• event of the actor that determines change of programmable
status
Configuration parameters of the words:
Remote Status word
• selection of actor (actor from 1 to 15) from which the word
(A÷D)
status is taken
• selection of the taken word
Active (Passive diagnosis) or deactivated (No diagnosis) cabled
Diagnostic
selectivity diagnosis
30 s, 1 min, 10 min, 60 min diagnosis frequency intervals
Diagnostic check timeout
available, if activated
Configuration of hardware selectivity (Only HW) or hardware
Zone Selectivity Type
and logic (Mixed)
Repeat Configuration
Interactive mask for selecting selectivity to be sent also to the
mask
upper levels (even if not active in the programmed device)
communication:
Information
Description
HW and Boot version
General module information
Flash CRC status and
Information about the correctness of the SW in the module
result
Ekip Link status
Signals Ethernet cable connection errors
SNTP Server Error
Error in communication with SNTP server
SNTP Server
State of synchronism with SNTP server
Synchronization
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP Master
IEEE 1558 status
Active) or absence (PTP Master but Passive) of a higher level master
Information
Line Congruency detection
Remote Programmable Status
Remote Status Word
Logic Zone Selectivity
Description
Information about the state and inconsistency of HW and logic
selectivity (state and type of selectivity inconsistent)
Status (true/false) of remote programmable statuses A, B, C and D
Value of remote programmable Words A, B, C, D
Logic selectivity states (inputs and outputs)
ABB | SACE Tmax XT
Default
ARP Enabled
Standard
mode
Local access
.
(2)
Default
0.0.0.0
Actor 1
None
None
1 global
No Diagnostic
30 seconds
HW only
0x0000
External electronic accessories | 9 - Ekip Link

Hide quick links:

Advertisement

Table of Contents
loading