124 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Continued from the previous page
Counters
(Sags Middle)
Last time stamp
Sags Middle
Sags Long
Actual number of S.
Actual [day -2 ... day -7]
number of S.
Counters
(Sags Middle)
Last time stamp
Sags Middle
Sags Long
Actual number of S.
Actual [day -2 ... day -7]
number of S.
Swells Certain counters relating to swells are available in the Counters - Day -1 and Counters - Cumulative submenus:
Counters
(Sags Middle)
Swells Short
Swells Long
The count refers to the reference menu interval (previous day or cumulative)
NOTE: since an event may fall under more than one category, only the counter of the main
type (long > short) is increased
Additional List
Counters
(Swells Short)
Last time stamp
Last value
Last duration
Actual number of S.
Actual [day -2 ... day -7]
number of S.
Counters
(Swells Long)
Last time stamp
Last value
Last duration
Actual number of S.
Actual [day -2 ... day -7]
number of S.
Description
Date and time of last recording of the Sags Middle counter
Value of last sag below the Sags Middle [V] threshold
Duration of last sag below the Sags Middle [ms] threshold
Sags Middle count of the current day
Sags Middle count of the last seven days of activity, calculated using the
internal clock of the unit
Description
Date and time of last recording of the Sags Long counter
Value of last sag below the Sags Long[V] threshold
Duration of last sag below the Sags Long[ms] threshold
Sags Long count of the current day
Sags Long count of the last seven days of activity, calculated using the internal
clock of the unit
Description
Counts the number of times that any line-to-line voltage exceeds the V swell Th
Short threshold for longer than V swell dur Short
Counts the number of times that any line-to-line voltage exceeds the V swell Th
Long threshold for longer than V swell dur Long
Description
Date and time of last recording of the Swells Short counter
Value of last swell above Swells Short [V] threshold
Duration of last swell above Swells Short[ms] threshold
Swells Short count for the current day
Swells Short count of the last seven days of activity, calculated using the
internal clock of the unit
Description
Date and time of last recording of the Swells Long counter
Value of last swell above Swells Long[V] threshold
Duration of last swell above Spikes[ms] threshold
Swells Long count for the current day
Swells Long count of the last seven days of activity, calculated using the
internal clock of the unit